Hasil Pencarian  ::  Simpan CSV :: Kembali

Hasil Pencarian

Ditemukan 1 dokumen yang sesuai dengan query
cover
Howongsakun, Teerachai
" The objective of this research was to study the effects of highly moist inlet air conditions such as temperature, relative humidity, and frontal air velocity on the value of the Lewis number (Le) in the cooling and dehumidifying process of air. A finned tube cooling coil was tested under ranges of temperature, relative humidity and frontal velocity. It was found that the Lewis number (Le) varied within the range of 0.92-1.62 and that the increase in inlet air ... "
2016
J-Pdf
Artikel Jurnal  Universitas Indonesia Library