Pemetaan Suhu Cool Room Penyimpanan Produk Warehouse D pada PT. Enseval Putera Megatrading Pulo Lentut = Temperature Mapping of the Product Storage Cool Room in Warehouse D at PT. Enseval Putera Megatrading Pulo Lentut

Dilfa Safnia Putri; Mahdi Jufri, supervisor (Fakultas Farmasi Universitas Indonesia, 2024)

 Abstrak

Penelitian ini bertujuan untuk memetakan suhu pada gudang penyimpanan produk (cool room) di PT. Enseval Putera Megatrading Pulo Lentut dengan mengidentifikasi titik suhu tertinggi (hot spot) dan terendah (cold spot) guna memastikan kestabilan suhu dalam rentang 15–25°C sesuai standar penyimpanan. Metode yang digunakan adalah kualifikasi pemetaan suhu menggunakan Termometer Data Logger 174-T. Proses pemetaan melibatkan pembuatan layout grid titik pengukuran, penempatan termometer data logger, perekaman data selama tujuh hari dengan interval 10 menit, serta analisis data menggunakan aplikasi Testo Comfort Software Basic 5.0. Hasil penelitian menunjukkan bahwa gudang cool room tidak memenuhi persyaratan suhu stabil 15–25°C. Suhu tertinggi tercatat sebesar 28,9°C (hot spot) pada titik 46, sedangkan suhu terendah tercatat sebesar 21°C (cold spot) pada titik 3. Dengan demikian, titik 46 dan titik 3 dapat dijadikan acuan dalam pemantauan suhu rutin untuk mengidentifikasi penyimpangan suhu yang berpotensi memengaruhi kualitas produk. Penelitian ini menggarisbawahi pentingnya pemantauan dan evaluasi rutin terhadap sistem penyimpanan guna memastikan kepatuhan terhadap standar suhu yang ditetapkan, sehingga kualitas produk tetap terjaga.

This study aims to map the temperature of the product storage warehouse (cool room) at PT. Enseval Putera Megatrading Pulo Lentut by identifying the highest temperature point (hot spot) and the lowest temperature point (cold spot) to ensure temperature stability within the 15–25°C range according to storage standards. The method used is a qualification of temperature mapping utilizing the 174-T Thermometer Data Logger. The mapping process involves creating a grid layout of measurement points, placing data loggers, recording data for seven days at 10-minute intervals, and analyzing the data using the Testo Comfort Software Basic 5.0 application. The results indicate that the cool room does not meet the stable temperature requirement of 15–25°C. The highest temperature was recorded at 28.9°C (hot spot) at point 46, while the lowest temperature was recorded at 21°C (cold spot) at point 3. Therefore, points 46 and 3 can serve as references for routine temperature monitoring to identify deviations that may affect product quality. This study emphasizes the importance of routine monitoring and evaluation of storage systems to ensure compliance with temperature standards and maintain product quality.

 File Digital: 1

Shelf
 PR-Dilfa Safnia Putri5.pdf :: Unduh

LOGIN required

 Metadata

Jenis Koleksi : UI - Tugas Akhir
No. Panggil : PR-pdf
Entri utama-Nama orang :
Entri tambahan-Nama orang :
Entri tambahan-Nama badan :
Program Studi :
Subjek :
Penerbitan : Depok: Fakultas Farmasi Universitas Indonesia, 2024
Bahasa : ind
Sumber Pengatalogan : LibUI ind rda
Tipe Konten : text
Tipe Media : computer
Tipe Carrier : online resource
Deskripsi Fisik : x, 31 pages : illustration